Performance analysis of ground water-source heat pump system with improved control strategies for building retrofit.
- 论文类型:
- 文章
- 第一作者:
- 朱娜
- 合写作者:
- 胡平放,王伟,喻建明,雷飞
- 发表刊物:
- Renewable Energy
- 收录刊物:
- SCI
- 所属单位:
- 华中科技大学
- 刊物所在地:
- Cyprus
- 学科门类:
- 工学
- 一级学科:
- 土木工程
- 项目来源:
- National Natural Science Foundation of China (NSFC)
- 文献类型:
- J
- 卷号:
- 80
- 页面范围:
- 324-330
- ISSN号:
- 0960-1481
- 关键字:
- Ground water-source heat pump; Retrofit technology; Improved operation methods
- DOI码:
- 10.1016/j.renene.2015.02.021
- 发表时间:
- 2015-08-01
- 影响因子:
- 8.634
- 摘要:
- This paper presented a case study on performance analysis of ground water-source heat pump system (GWHP) for a hotel building retrofit Splitting air-conditioner was used for cooling and coal fired boiler was used for heating in original system. The GWHP system could save electricity energy and water source consumption under improved operation methods compared with the common operation methods. In this study, the experimental average cooling coefficient of performance (COP) of the units and system were 5.53 and 3.29, respectively (from Jun. to Sep.). The average heating COP of the units and system were 4.45 and 2.79, respectively (from Nov. to Feb.). The primary energy consumption of GWHP system was reduced by 42.9% when compare with the original cooling/heating system in a year. The indoor air temperature fluctuated in comfortable range (19.3 degrees C-24.4 degrees C) during test day in winter. The results show that the GWHP system was particularly suitable for this hotel under our improved operation methods. This renewable and environment-friendly technology could promote energy conservation and sustainability obviously for the hotel building